Stair building regulations
The limits Approved Document K sets for the steps of a staircase in England, in one place. Work out your own stair with the stair calculator.
Rise and going
The rise is the height of each step. The going is the depth of each tread, measured nosing to nosing. Every step in a flight should have the same rise and going.
| Kind of stair | Rise | Going |
|---|---|---|
| Private stair a stair in a home | 150 to 220 mm | 220 to 300 mm |
| Utility stair escape stairs and stairs used by few people, not in homes | 150 to 190 mm | 250 to 400 mm |
| General access stair stairs in public and shared buildings | 150 to 170 mm | 250 to 400 mm |
For every kind of stair, twice the rise plus the going should come to between 550 mm and 700 mm. A private stair should be no steeper than 42°.
Number of steps in a flight
Outside homes, a utility stair should have no more than 16 risers between landings, and a general access stair no more than 12, or exceptionally up to 16 in small premises where space is tight.
Headroom
Allow at least 2 m of headroom over the stair, measured up from the pitch line. In a loft conversion where there is not room for that, 1.9 m at the centre of the stair and 1.8 m at the side is acceptable.
Guarding
In a home, the sides of a flight or landing need guarding where there is a drop of more than 600 mm.
Where this comes from
Approved Document K: protection from falling, collision and impact, 2013 edition (GOV.UK). It applies in England; Wales, Scotland and Northern Ireland have their own building regulations. Approved Documents are guidance on meeting the regulations: your building control body decides whether work meets them. Checked 13 November 2026.